Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) x Insufficient machine room lighting 11/22/2022
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 NEC - label location of the feeder panel on the disconnect 7/23/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x No active telephone 11/22/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 x No lockable machine room door 11/22/2022
MO Minimum : Elevators (H) - Machine Rooms (H)7 x x No main line disconnect 11/22/2022
MO Minimum : Elevators (S) - Fire Service (S)1 x x No smoke detectors or heat detector 11/22/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting open egg crate ceiling in elevator cab, provide covers for the light tubes 11/11/2021
MO Minimum : Elevators (I) - Pits (I)1 pit has water/oil mixture several inches deep - sump pump not working 11/11/2021
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) pit light switch broke, turned on but will not turn off 11/11/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate post current copy of the state operating certificate in the machine space 11/11/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements replace worn out roller guides 8/3/2020