Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency Light and Bell do not work when normal power is removed (Reinspect) 7/3/2023
MO Minimum : Elevators (I) - Pits (I)1 pits shall be kept clean of dirt and rubbish
MO Minimum : Elevators (I) - Pits (I)1 All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Telephone in car. Replace Backup Battery increase volume. 6/16/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Provide Phase I Fire Service Instructions at main egress landing. The placard is missing
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Door Close and Door Open button do not work.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts x Auxiliary Power fails to bring the car down and open the doors when normal power is removed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace the slide guides that are missing on the top and bottom of the car
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Auxiliary Power fails to bring the car down and open the doors when normal power is removed. 6/10/2024
conversion conversion n/a Replace backup battery on telephone in car 10/2/2020