Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No 8.6.1.4.11 Fire Service Testing must be documented monthly. The form is present in the MCP, but hasn't been logged monthly .
A17.1-1996 : Elevators 2.4 - Machine space 100.3d No No Machine room lighting needs to be repaired, 1 or more bulbs not working.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current State Operating Permit shall be obtained and displayed in the Equipment Room. 2018 displayed.
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) Yes Yes The hoist ropes are rouged and undersized and require replacement. Unit Red Tagged 2/3/2020
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current state operating certificate shall be posted in the elevator machine room. 2/25/2020
A17.1-1996 : Elevators 1.16 - Rated load, platform area, and data plate 1001.2(a)(16) No No A code data plate shall be provided. It shall read: A17.1-1996 & A17.3-1996 2/25/2020
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 No No A monthly fire service testing log shall be kept on site. 2/25/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone shall work. 7/16/2024