MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work.
|
12/9/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator.
|
1/22/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
x
|
|
The means to restrict opening of the car door shall be operational.
|
1/22/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
The means to restrict opening of the car door are not operational between floors 1 & 2 and Basement & 1.
|
3/9/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The emergency/standby power shall be tested.
|
10/15/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Fire service operation shall be tested as required.
|
10/15/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Two-way communication device shall give proper location message. No location message is being given.
|
10/21/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator.
|
10/21/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Fire service operation shall be tested.
|
10/21/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Testing incomplete. Need all weight tests: 125% down run, 100% set safeties, 100% car buffer, empty car counterweight buffer test, slide.
|
10/21/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Two-way communication device shall give proper location message. No location message is being given.
|
10/24/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Testing incomplete. Need all weight tests: 125% down run, 100% set safeties, 100% car buffer, empty car counterweight buffer test, slide.
|
10/24/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Fire service testing must be properly documented monthly on log sheet. The logs are blank.
|
1/26/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Compliant/required documentation shall be kept in equipment room (neat/organized) including MCP, wiring diagrams, PM log, callback log, and evacuation procedures.
|
1/26/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Non-elevator related items (HVAC fans, etc..) shall not be stored in the machine room.
|
1/26/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2 On-Site Documentation
|
|
|
A code compliant MCP and all the on-site documentation required shall be provided in the machine room.
|
11/25/2024
|