Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone not working. 4/1/2019
MO Minimum : Elevators (I) - Pits (I)1 No No Clean oil out of pit. 6/27/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No OSV in pit is not sealed. Perform OSV test on or before next annual inspection. 1/18/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No No Provide on-site maintenance control program. 1/18/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Car failed 15 min stand test. Tech determined leaking back through valve. Repair/replace as needed. Reinspect 1/18/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Phone in elevator cab does not work. Phone line has no power. 5/6/2024