Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2b (Clean Machine Room) 1206.2c - Clean the car top. 10/8/2019
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide a code compliant MCP including onsite documents. 7/10/2024
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. 7/10/2024
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) The car top shall be kept clean. Clean the car top. 7/10/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Pits shall be kept clean. Clean the pit. 7/10/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The emergency power indicator light shall activate when unit is operating on emergency power. 7/10/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 7/10/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be kept on site. 7/10/2024
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2c (Clean Car Tops) The car top is dirty. Clean the car top. 7/10/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x The standby/emergency power indicator light at the egress floor shall illuminate when on emergency power operation. 3/6/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 2/22/2022
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x The in car emergency lighting shall be operational. 2/22/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency alarm bell shall be operational when the 110v source is removed. 2/22/2022
A17.1-1996 : Elevators 2.17 - Drive machine brake 210.8 x The brake switches shall be operational. 2/22/2022