Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 the check valve did not hold the elevator during the set test, elevator settled over 3 inches in 15 minutes, when the gate valve was closed the elevator did not move, repair or replace the valve. 11/10/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x only one emergency light bulb came on, replace burnt out bulb. 11/10/2021
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 x the elevator settled 9 inches during 15 minute set test, shut the gate valve in the machine room and the elevator didn't settle at all, repair or replace the valve 3.19.4.3 6/30/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts replace the packing gland on the jack, pit bucket is overflowing between visits 8/24/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x emergency phone not working, no dial tone 7/11/2023