MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
emergency phone not working, no dial tone
|
7/11/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
only one emergency light bulb came on, replace burnt out bulb.
|
11/10/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
replace the packing gland on the jack, pit bucket is overflowing between visits
|
8/24/2023
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
|
|
the check valve did not hold the elevator during the set test, elevator settled over 3 inches in 15 minutes, when the gate valve was closed the elevator did not move, repair or replace the valve.
|
11/10/2021
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
x
|
|
the elevator settled 9 inches during 15 minute set test, shut the gate valve in the machine room and the elevator didn't settle at all, repair or replace the valve 3.19.4.3
|
6/30/2023
|