Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a The emergency car lighting could not be tested due to the test button malfunctioning. The test button on the fixture shall be repaired to operate. 10/20/2020
conversion conversion n/a The emergency alarm bell could not be tested due to the test button malfunctioning. The test button on the fixture shall be repaired to operate. 10/20/2020
conversion conversion n/a The elevator car door closing force is over the maximum allowable force of 30lbs. Readjust door closing force to be less than 30lbs. 10/20/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements The ventilation cooling fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed. Per Asst. State Fire Marshall Greg Carrell, G.1 is the correct code section for this violation. 10/20/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required.Per Asst. State Fire Marshall Greg Carrell, G.1 is the correct code section for this violation. 10/20/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements The emergency car lighting could not be tested due to the test button malfunctioning. The test button on the fixture shall be repaired to operate. Per Asst. State Fire Marshall Greg Carrell, G.1 is the correct code section for this violation.. 10/20/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements The emergency alarm bell could not be tested due to the test button malfunctioning. The test button on the fixture shall be repaired to operate. Per Asst. State Fire Marshall Greg Carrell, G.1 is the correct code section for this violation. 10/20/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements The ventilation cooling fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed. 10/20/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x 8.6.4.15 Car Emergency Systems - The emergency car lighting is not operational, likely indicating that the light bulbs need replacement. The fixture shall be repaired to operate. 8/13/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: In phase II operation, the elevator car will not override the security feature on the car operating panel. Security shall be overridden in fireman’s service. 8/13/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements The ventilation cooling fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed. 10/20/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x The front car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. 10/29/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts The ventilation cooling fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed. 8/10/2021
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The pit light fixtures failed to illuminate in the pit. Repair pit light fixtures to provide lighting of not less than five (5) foot candles at the pit floor for maintenance and emergency personnel.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The testing has not been completed on the elevator at this time. The backup emergency power and fireman’s service shall be tested before the inspection is completed. 8/16/2022