Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Clean pit to remove debris, water, and/or oil and address sources. 11/22/2023
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b The ventilation in the machine room is marginally efficient to keep the elevator controller at its required temperature for operation. At this time, the elevator maintenance contractor has the elevator controller doors open with a small ventilation fan keeping the operating temperature sufficient for the elevator controller, which does not meet the code requirement. Upgrade the elevator machine room ventilation.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams The elevator controller has a temporary jumper in use for a resistor that has failed. Repair controller and remove the temporary jumper.
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b The ventilation in the machine room is marginally efficient to keep the elevator controller at its required temperature for operation. At this time, the elevator maintenance contractor has the elevator controller doors open with a small ventilation fan keeping the operating temperature sufficient for the elevator controller, which does not meet the code requirement. Upgrade the elevator machine room ventilation.
A17.1-1996 : Elevators 4.2 - Hoistway doors 1001.2(d)(2) 8.6.4.13 door systems Hoistway door retaining gibs are missing on the hoistway doors at the 4th and 3rd landing. Reinstall hoistway door gibs.
MO Minimum : Elevators (I) - Pits (I)1 The elevator pit floor is covered in dust and debris. The pit shall be cleaned.
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b The ventilation in the machine room is marginally efficient to keep the elevator controller at its required temperature for operation. At this time, the elevator maintenance contractor has the elevator controller doors open with a small ventilation fan keeping the operating temperature sufficient for the elevator controller, which does not meet the code requirement. Upgrade the elevator machine room ventilation.
A17.1-1996 : Elevators 4.2 - Hoistway doors 1001.2(d)(2) 8.6.4.13 door systems Hoistway door retaining gibs are missing on the hoistway doors at the 4th and 3rd landing. Reinstall hoistway door gibs.
A17.1-1996 : Elevators 2.6 - Ventilation 1001.2(b)(6) The ventilation cooling fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed. 10/20/2020
A17.1-1996 : Elevators 2.6 - Ventilation 1001.2(b)(6) The ventilation in the machine room is marginally efficient to keep the elevator controller at its required temperature for operation. At this time, the elevator maintenance contractor has the elevator controller doors open with a small ventilation fan keeping the operating temperature sufficient for the elevator controller, which does not meet the code requirement. Upgrade the elevator machine room ventilation. 10/20/2020
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 1001.2(a)(18) x The front car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection required. 7/13/2022
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a x The elevator pit shall be cleaned of dust and debris. 7/17/2019
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x The emergency light fixture inside the elevator is not operational and shall be repaired. Reinspection required. 1/31/2024