MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams
|
|
|
The elevator controller has a temporary jumper in use for a resistor that has failed. Repair controller and remove the temporary jumper.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The elevator pit floor is covered in dust and debris. The pit shall be cleaned.
|
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
1001.2(a)(18)
|
x
|
|
The front car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection required.
|
7/13/2022
|
A17.1-1996 : Elevators
|
2.6 - Ventilation
|
1001.2(b)(6)
|
|
|
The ventilation cooling fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed.
|
10/20/2020
|
A17.1-1996 : Elevators
|
2.6 - Ventilation
|
1001.2(b)(6)
|
|
|
The ventilation in the machine room is marginally efficient to keep the elevator controller at its required temperature for operation. At this time, the elevator maintenance contractor has the elevator controller doors open with a small ventilation fan keeping the operating temperature sufficient for the elevator controller, which does not meet the code requirement. Upgrade the elevator machine room ventilation.
|
10/20/2020
|
A17.1-1996 : Elevators
|
4.2 - Hoistway doors
|
1001.2(d)(2)
|
|
|
8.6.4.13 door systems Hoistway door retaining gibs are missing on the hoistway doors at the 4th and 3rd landing. Reinstall hoistway door gibs.
|
|
A17.1-1996 : Elevators
|
4.2 - Hoistway doors
|
1001.2(d)(2)
|
|
|
8.6.4.13 door systems Hoistway door retaining gibs are missing on the hoistway doors at the 4th and 3rd landing. Reinstall hoistway door gibs.
|
|
A17.1-1996 : Elevators
|
2.6 - Ventilation
|
101.5b
|
|
|
The ventilation in the machine room is marginally efficient to keep the elevator controller at its required temperature for operation. At this time, the elevator maintenance contractor has the elevator controller doors open with a small ventilation fan keeping the operating temperature sufficient for the elevator controller, which does not meet the code requirement. Upgrade the elevator machine room ventilation.
|
|
A17.1-1996 : Elevators
|
2.6 - Ventilation
|
101.5b
|
|
|
The ventilation in the machine room is marginally efficient to keep the elevator controller at its required temperature for operation. At this time, the elevator maintenance contractor has the elevator controller doors open with a small ventilation fan keeping the operating temperature sufficient for the elevator controller, which does not meet the code requirement. Upgrade the elevator machine room ventilation.
|
|
A17.1-1996 : Elevators
|
2.6 - Ventilation
|
101.5b
|
|
|
The ventilation in the machine room is marginally efficient to keep the elevator controller at its required temperature for operation. At this time, the elevator maintenance contractor has the elevator controller doors open with a small ventilation fan keeping the operating temperature sufficient for the elevator controller, which does not meet the code requirement. Upgrade the elevator machine room ventilation.
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Clean pit to remove debris, water, and/or oil and address sources.
|
11/22/2023
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a
|
x
|
|
The elevator pit shall be cleaned of dust and debris.
|
7/17/2019
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
The emergency light fixture inside the elevator is not operational and shall be repaired. Reinspection required.
|
1/31/2024
|