MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The elevator pit shall be cleaned of dust and debris.
|
10/20/2020
|
conversion
|
conversion
|
n/a
|
|
|
There is no fireman?s emergency service phase I instruction signage adjacent to the keyed switch at the primary egress floor, as required.
|
10/20/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. Per Asst. State Fire Marshall Greg Carrell, G.1 is the correct code section for this violation.
|
10/20/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
The car door restrictor device shall be repaired to properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required.
|
8/12/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
The fireman's emergency service phase I and II operations were tested and the following deficiencies were noted: There is no fireman’s emergency service phase II instruction signage adjacent to the keyed switch in the car, as required
|
8/12/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
The fireman's emergency service phase I and II operations were tested and the following deficiencies were noted: The “Door Open” button did not work in phase II.
|
8/12/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
The front car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required.
|
10/29/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The testing has not been completed on the elevator at this time. The backup emergency power and fireman’s service shall be tested before the inspection is completed.
|
8/16/2022
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
x
|
|
When sprinkler systems are present in the hoistway, means shall be provided to automatically disconnect the main power supply to the affected elevator prior to the application of water. A smoke detector shall also be installed to recall the elevator before the power is removed before the application of water.
|
|