Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)16 x When sprinkler systems are present in the hoistway, means shall be provided to automatically disconnect the main power supply to the affected elevator prior to the application of water. A smoke detector shall also be installed to recall the elevator before the power is removed before the application of water.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements The elevator car door restrictor did not operate when tested. The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. Per Asst. State Fire Marshall Greg Carrell, G.1 is the correct code section for this violation. 10/20/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x The car door restrictor device shall be repaired to properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. 8/12/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements The oil cooling unit did not operate when activated on the day of inspection. Repair the cooling unit to operate as designed. 10/20/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. 10/29/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements The oil cooling unit did not operate when activated on the day of inspection. Repair the cooling unit to operate as designed. 10/20/2020
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. 10/20/2020
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 A Victaulic fitting is noticeably leaking oil in the hoistway. Repair the fitting with an adequately sized valve. 10/20/2020
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 The oil cooling unit did not operate when activated on the day of inspection. Repair the cooling unit to operate as designed. 10/20/2020
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x The fireman's emergency service phase I and II operations was tested and the following deficiency was noted:The visual signal device did not light in the car when phase I was activated. Reinspection is required. 3/24/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The testing has not been completed on the elevator at this time. The backup emergency power and fireman’s service shall be tested before the inspection is completed. 8/16/2022
conversion conversion conversion - reinspect x The elevator car door restrictor did not operate when tested. The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. 8/22/2018
conversion conversion n/a A Victaulic fitting is noticeably leaking oil in the hoistway. Repair the fitting with an adequately sized valve. 10/20/2020
conversion conversion n/a There is no fireman?s emergency service phase I instruction signage adjacent to the keyed switch at the primary egress floor, as required. 10/20/2020