Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements The hoistway doors are missing pick up rollers for the car door clutch to work properly. Replace missing pick up rollers. Per Asst. State Fire Marshall Greg Carrell, G.1 is the correct code section for this violation. 8/18/2020
MO Minimum : Elevators (I) - Pits (I)1 The elevator pit shall be cleaned of dust and debris. 8/18/2020
MO Minimum : Elevators (I) - Pits (I)1 The elevator pit shall be cleaned of dust and debris (biohazard debris may be present). 8/18/2020
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. 8/18/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts A direction arrow on the 1st landing call station is pushed in resulting in a possible electrical hazard and shall be repaired. 11/22/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection There is no oil leakage container in the pit. The container shall not be over 5 gallons and shall be covered.