MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
Provide a written maintenance control program
|
11/8/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The elevator machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key.
|
10/17/2018
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. A telephone cabinet has been dislodged from the wall that is impeding the area for proper maintenance to be performed.
|
10/17/2018
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Repair machine room door closer. Door to be self-closing and locking.
|
12/31/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Increase machine room lighting to 10 ft candles throughout, measured at the floor.
|
12/31/2020
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7
|
x
|
|
Cab lights need to be repaired or replaced to provide code compliant lighting.
|
1/21/2025
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The phone inside the car does not work.
|
1/21/2025
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency communication line does not work.
|
1/21/2025
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
There is a sprinkler at the top of hoistway, but no heat or smoke detector.
|
1/21/2025
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
x
|
|
The distance between the face of the controller and the nearest obstruction shall be no less than 36".
|
1/21/2025
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
x
|
|
The distance between the face of the controller and the nearest obstruction shall be no less than 36". Note: Customer may be applying for a variance.
|
|
conversion
|
conversion
|
n/a
|
|
|
The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety.
|
10/17/2018
|