Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No There is a sprinkler at the top of hoistway, but no heat or smoke detector. 1/21/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No The elevator machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. 10/17/2018
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Repair machine room door closer. Door to be self-closing and locking. 12/31/2020
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. A telephone cabinet has been dislodged from the wall that is impeding the area for proper maintenance to be performed. 10/17/2018
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Increase machine room lighting to 10 ft candles throughout, measured at the floor. 12/31/2020
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 2.14.7 Yes No Cab lights need to be repaired or replaced to provide code compliant lighting. 1/21/2025
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 Yes No The distance between the face of the controller and the nearest obstruction shall be no less than 36". 1/21/2025
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 Yes No The distance between the face of the controller and the nearest obstruction shall be no less than 36". Note: Customer may be applying for a variance.
A17.1-2016 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency communication line does not work. 1/21/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The phone inside the car does not work. 1/21/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No No Provide a written maintenance control program 11/8/2021
conversion conversion n/a No No The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. 10/17/2018