Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)2 No key on site to get into Elevator equipment room. Person that had a key was not able to come to building to open door. Inspection not completed. Reinspection required.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Phone is not working. 3/31/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Phone does not work 10/11/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 Repair ceiling in machine room 12/2/2024
MO Minimum : Elevators (H) - Machine Rooms (H)2 Ceiling missing in elevator equipment room. Water line/drain running over elevator controller needs to be quarded or guttered 12/2/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher by elevator equipment room needs to be serviced. 1/2/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Fire service Phase II Operating instructions need to be replaced inside car by Phase II Fire service key switch 1/2/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 Non-elevator related stuff needs to be removed from elevator equipment room 1/2/2025
MO Minimum : Elevators (I) - Pits (I)1 Need to install a non-combustible sump hole cover flush with pit floor 1/2/2025