Install Box covers on all uncovered electrical boxes
|
8/21/2018
|
conversion
|
conversion
|
n/a
|
|
|
Remove unused and Excessive draped flex conduit.Shorten as needed fasten to wall and cieling
|
8/21/2018
|
conversion
|
conversion
|
n/a
|
|
|
Shorten hoist ropes c measurment
|
8/21/2018
|
conversion
|
conversion
|
n/a
|
|
|
Furnish permanent outlet for air conditioner (no extension cords)
|
8/21/2018
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Provide permanent means of water removal from the elevator pit.
|
8/9/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
The elevator buffer has been submerged recently resulting in water contaminating the oil reservoir for the buffer. The car buffer shall be cleaned/contaminated water removed and the proper weight buffer oil used in the reservoir.
|
8/7/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor.
|
8/7/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit light does not work
|
8/3/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current operating certificate shall be displayed in the machine room
|
3/21/2024
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Light in pit shall work
|
3/21/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required.
|
5/4/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required.
|
5/4/2021
|