Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a No No replace hoist cables - 3 months to accomplish 7/24/2018
conversion conversion n/a No No CPR handriail missing - 3 months to accomplish 7/24/2018
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Pit light not working. 11/26/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Replace machine tie down isolation pads that are deteriorated. 3/17/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Test incomplete, need to test fire service to complete testing. Re-inspection required 8/26/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Elevator ceased operation during testing. Machine room emergency light, alarm, phone and door closing force were the only tests performed. Need to perform all other tests to complete inspection. Re-inspection required 2/28/2025
A17.1-2016 : Elevators 3.23 - Suspension Means 8.6.3.2 (Re-Inspection) Yes No Suspension cables are rouged & undersized. Replace suspension cables. Re-inspection required