Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2 way communication is not working. Re-inspection required 2/9/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements 8.6.5.14.3(f) Auxiliary Lowering fails to bring the car down to a lower landing and open the doors. Dead Battery.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency Phone in car fails to establish two-way communication 3/26/2024
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Phase Two Fire service sign inside of the elevator cab needs to be replaced. 8/13/2020
conversion conversion n/a The hydraulic pump motor failed during testing and shall be replaced before the elevator can be returned to service. 9/5/2018