Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service (S)1 x Elevator door at 6th floor shall not be locked from outside. Car does not have access to all floors on Phase II fire recall operation. Inoperative. Repair Phase I recall. Independent service not overridden. 3/16/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher shall be placed in the machine room
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Elevator door at the 6th floor shall not be bolted shut, the elevator still stops at the 6th floor. Elevator does not have access to all floors on phase 2 fire service. Independent service is not overridden on phase 1 fire service recall. This is the second time this has been written up. Requires a reinspection