Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Must Make Emergency Alarm operable. 1.6 6/5/2024
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Car Emergency System (Re-Inspection) x Cab lighting circuit being used to supply power door reopen device (NEC 620.22) 4/5/2022
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5.1 Examination and Maintenance Jack seal needs to be replaced 2/14/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.4 - Machine space 2.7.1.1 Provide a chainlink fence seperating the machine room from the other equipment serving the building not pretaining to the operation of the elevator 5/21/2020
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation No Records 2/14/2022
A17.1-2016 : Elevators 2.5 - Housekeeping 8.11.3.1.2(h) Pump unit oil pan required to be pumped out 2/14/2022
A17.1-2016 : Elevators 2.9 - Guarding of exposed auxiliary equipment 8.11.3.1.2(l) Install proper cover for pump & motor 2/14/2022
conversion conversion n/a Povide a light switch in the pit accessable to the lowest landing door. 7/31/2018
conversion conversion n/a Enclose the elevator equipment with a 6 foot high chain link fence with a self closing self latching gate with a lock always locked outside never locked inside. maintain a minimum of 36 inches clear working splace around the equipment. 7/31/2018
conversion conversion n/a Provide a capacity plate in the car. stating 2000 lb. capacity. 7/31/2018
conversion conversion n/a Clean the machine spaace of combustibles, ie leaves, wood etc. anso the pit is very dirty and needs cleaned 7/31/2018
conversion conversion n/a Replace the burnt out lights in the machine room 7/31/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Obtain and display a current state operating certificate in the machine room. This was on last years inspection too. 5/21/2020