Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No MACHINE ROOM shall have proper commercial Fire Extinguisher and shall have current monthly/annual test tag 4/7/2026
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No MACHINE ROOM - lighting needs to be repaired, fixture is loose and needs to be securely attached to ceiling. 4/7/2026
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Non-elevator related items shall not be stored in Machine Room. Remove carpet remnants, etc 4/7/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No MACHINE ROOM - Heat detector is falling from its box. Repair. 4/7/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag. 4/6/2026
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Lighting needs to be repaired, fixture is loose and needs to be securely attached to celling. 4/6/2026
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Non-elevator related items shall not be stored in Machine Room. Remove carpet remnants, etc. 4/6/2026
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No 2-way communication shall work. 4/6/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No The door close button shall be operational. 7/14/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 7/14/2022
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes The door close button does not work. Phase 2 fire service cannot operate without a functioning door close button in the elevator. Phase 2 fire service shall be code compliant. This is the only elevator in the building, therefore the elevator was left in service. This deficiency must be corrected in 15 days or the elevator will be turned off and red tagged. 5/16/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Provide a code compliant MCP including onsite documents. 6/3/2021