Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.19 - Gears, bearings, and flexible couplings 1001.2(b)(17) - no reinspect No No A grease seal on the drive machine is leaking excessively and shall be replaced. 12/11/2019
A17.1-1996 : Elevators 3.10 - Hoistway construction 1001.2(c)(16) No No A temporary construction barrier was installed in the elevator hoistway between the elevator cars. This barrier is designed for only temporary use and shall be removed from the hoistway. 12/11/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) Yes No Car door restrictor is not working. Re-inspection required 5/16/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Car top needs to be cleaned 8/19/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit No No Clean debris and dirt from elevator hoistway 8/19/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Elevator car top needs to be cleaned 8/19/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Elevator cartop needs to be cleaned 9/13/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No Emergency power was tested and elevator will not take calls, stuck in lobby. Take corrective action and re-test. 1/17/2025
A17.1-1996 : Elevators 3.20 - Governor rope 1001.2(c)(26) Yes No Excessive rouging on Governor rope, needs to be replaced with in 30 days. Re-inspection required 5/16/2023
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 210.4 No No Fire sprinklers are present in the elevator hoistway and pit. A shunt trip disconnect shall be added and electrically tied into the heat detectors to remove power from the elevator before the application of water. REINSPECTION REQUIRED. 9/1/2020
A17.1-1996 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 210.4 No No Fire sprinklers are present in the elevator hoistway and pit. A shunt trip disconnects shall be added and electrically tied into the heat detectors to remove power from the elevator before the application of water. Reinspection and testing will be required 5/18/2020
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 210.4 No No Fire sprinklers are present in the elevator hoistway and pit. A shunt trip disconnects shall be added and electrically tied into the heat detectors to remove power from the elevator before the application of water. Reinspection and testing will be required. 12/11/2019
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes No Governor rope has excessive rouging and needs replaced 9/5/2024
A17.1-1996 : Elevators 3.23 - Suspension rope 212 Yes No Hoist ropes are undersized and rouged and meet the criteria for replacement. Take corrective action as needed. 1/17/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Missing ceiling tiles inside elevator. Take corrective action as needed. 1/23/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit No No Need to clean debris and dirt from elevator hoistway 9/13/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance No No Need to replace leaking seal on elevator traction machine 9/13/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Performed test to check elevator on emergency power. After the elevator was transferred to emergency power, the elevator would not run. All operating parameters were lost in elevator controller. Repair elevator to transfer seamlessly to operate on emergency power. Re-inspection required
conversion conversion conversion - reinspect Yes No Phone not working. 6/21/2018
MO Minimum : Elevators (I) - Pits (I)1 No No Pit & hoistway needs to be cleaned of debris, oil & lint. 8/19/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Replace leaking seal on elevator traction machine 8/19/2024
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.6.4.11 Runby (Re-Inspect) Yes No Ropes need to be shortened, counterweight run by is not sufficient, minimum 6". 1/17/2025
A17.1-1996 : Elevators 2.19 - Gears, bearings, and flexible couplings 1001.2(b)(17) Yes No Seal on machine is leaking excessively and is causing oil to leak down on top of car top, needs to be replaced. Re-inspection required 5/16/2023
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 No No The cab ceiling is of the open egg-crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers. 12/11/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The elevator ADA telephone inside the elevator is not working properly. Check and repair the programming of this phone for proper operation and passenger safety. Reinspection required. 6/1/2020
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) No No The elevator machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. The door currently does not lock securely. 12/11/2019
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 Yes No There are 2 phase I fire service key switches at the main lobby landing hall call buttons. The primary switch with bypass, off and on is not functioning. The 2nd switch with off and on only, does recall the elevator to the main lobby landing. Repair non functional phase I key switch. Also call cancel and hold function does not work on phase II fire service, needs repaired. Re-inspection required
A17.1-1996 : Elevators 2.14 - Code data plate 215 No No There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to, as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. Upon investigation, it has been determined that the last major alteration occurred on 11/23/1999. The proper code edition that this elevator was installed to is A17.1 1996. 12/11/2019