A17.1-1996 : Elevators
|
2.19 - Gears, bearings, and flexible couplings
|
1001.2(b)(17) - no reinspect
|
|
|
A grease seal on the drive machine is leaking excessively and shall be replaced.
|
12/11/2019
|
A17.1-1996 : Elevators
|
3.10 - Hoistway construction
|
1001.2(c)(16)
|
|
|
A temporary construction barrier was installed in the elevator hoistway between the elevator cars. This barrier is designed for only temporary use and shall be removed from the hoistway.
|
12/11/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
Car door restrictor is not working. Re-inspection required
|
5/16/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
Car top needs to be cleaned
|
8/19/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.7 Cleaning of Hoistway and Pit
|
|
|
Clean debris and dirt from elevator hoistway
|
8/19/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
Elevator car top needs to be cleaned
|
8/19/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
Elevator cartop needs to be cleaned
|
9/13/2024
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
211.2
|
x
|
|
Emergency power was tested and elevator will not take calls, stuck in lobby. Take corrective action and re-test.
|
|
A17.1-1996 : Elevators
|
3.20 - Governor rope
|
1001.2(c)(26)
|
x
|
|
Excessive rouging on Governor rope, needs to be replaced with in 30 days. Re-inspection required
|
5/16/2023
|
A17.1-1996 : Elevators
|
2.11 - Disconnecting Means and Control
|
210.4
|
|
|
Fire sprinklers are present in the elevator hoistway and pit. A shunt trip disconnect shall be added and electrically tied into the heat detectors to remove power from the elevator before the application of water. REINSPECTION REQUIRED.
|
9/1/2020
|
A17.1-1996 : Elevators
|
2.10 - Numbering of elevators, machines, and disconnect switches
|
210.4
|
|
|
Fire sprinklers are present in the elevator hoistway and pit. A shunt trip disconnects shall be added and electrically tied into the heat detectors to remove power from the elevator before the application of water. Reinspection and testing will be required
|
5/18/2020
|
A17.1-1996 : Elevators
|
2.11 - Disconnecting Means and Control
|
210.4
|
|
|
Fire sprinklers are present in the elevator hoistway and pit. A shunt trip disconnects shall be added and electrically tied into the heat detectors to remove power from the elevator before the application of water. Reinspection and testing will be required.
|
12/11/2019
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Governor rope has excessive rouging and needs replaced
|
9/5/2024
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
212
|
x
|
|
Hoist ropes are undersized and rouged and meet the criteria for replacement. Take corrective action as needed.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Missing ceiling tiles inside elevator. Take corrective action as needed.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.7 Cleaning of Hoistway and Pit
|
|
|
Need to clean debris and dirt from elevator hoistway
|
9/13/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.1 Examination and Maintenance
|
|
|
Need to replace leaking seal on elevator traction machine
|
9/13/2024
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Phone not working.
|
6/21/2018
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit & hoistway needs to be cleaned of debris, oil & lint.
|
8/19/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Replace leaking seal on elevator traction machine
|
8/19/2024
|
A17.1-1996 : Elevators
|
2.19 - Gears, bearings, and flexible couplings
|
1001.2(b)(17)
|
x
|
|
Seal on machine is leaking excessively and is causing oil to leak down on top of car top, needs to be replaced. Re-inspection required
|
5/16/2023
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
The cab ceiling is of the open egg-crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers.
|
12/11/2019
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The elevator ADA telephone inside the elevator is not working properly. Check and repair the programming of this phone for proper operation and passenger safety. Reinspection required.
|
6/1/2020
|
A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
1001.2(b)(1)
|
|
|
The elevator machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. The door currently does not lock securely.
|
12/11/2019
|
A17.1-1996 : Elevators
|
2.14 - Code data plate
|
215
|
|
|
There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to, as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. Upon investigation, it has been determined that the last major alteration occurred on 11/23/1999. The proper code edition that this elevator was installed to is A17.1 1996.
|
12/11/2019
|