Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 No No The cab ceiling is of the open egg-crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers. 12/11/2019
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) No No The elevator machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. The door currently does not lock securely. 12/11/2019
A17.1-1996 : Elevators 2.14 - Code data plate 215 No No There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to, as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. Upon investigation, it has been determined that the last major alteration occurred on 11/23/1999. The proper code edition that this elevator was installed to is A17.1 1996. 12/11/2019
A17.1-1996 : Elevators 2.19 - Gears, bearings, and flexible couplings 1001.2(b)(17) - no reinspect No No A grease seal on the drive machine is leaking excessively and shall be replaced. 12/11/2019
A17.1-1996 : Elevators 3.10 - Hoistway construction 1001.2(c)(16) No No A temporary construction barrier was installed in the elevator hoistway between the elevator cars. This barrier is designed for only temporary use and shall be removed from the hoistway. 12/11/2019
A17.1-1996 : Elevators 3.23 - Suspension rope 212 Yes No Hoist ropes are undersized and rouged and meet the criteria for replacement. Take corrective action as needed. 1/17/2025
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No Emergency power tested and elevator will not take calls. Stuck on 9th floor. Take corrective action and re-test. 1/17/2025
A17.1-1996 : Elevators 1.3 - Operating control devices 210.1a Yes No Lobby call button is stuck and does not work. Take corrective action. 1/17/2025
A17.1-1996 : Elevators 1.17 - Standby power operation 1002.2g (Standby Power Operation) Yes No Performed test to check elevator on emergency power. After the elevator was transferred to emergency power, the elevator would not run. All operating parameters were lost in elevator controller. Repair elevator to transfer seamlessly to operate on emergency power. Re-inspection required 3/23/2026
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Alarm bell in elevator cab does not work, needs repaired. Re-inspection required 3/23/2026
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 102.2 Yes No All duct covers must be installed before 2nd elevator is turned over.
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures Yes No Heat and smoke detectors must be tested again before 2nd elevator is turned over.
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.6.4.11 Runby (Re-Inspect) Yes No Ropes need to be shortened, counterweight runby is not sufficient, minimum 6". 1/17/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 Yes Yes Phase I & Phase II fire service did not work. Elevator removed from service and Red-tagged. Re-inspection required 4/24/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Performed test to check elevator on emergency power. After the elevator was transferred to emergency power, the elevator would not run. All operating parameters were lost in elevator controller. Repair elevator to transfer seamlessly to operate on emergency power. Re-inspection required 4/24/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Alarm bell in elevator cab does not work. Need to repair alarm bell. Re-inspection required 4/24/2025
conversion conversion conversion - reinspect Yes No Phone not working 6/21/2018
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes No Governor rope is rouging excessively and shall be replaced within 90 days. Re-inspection required 5/16/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Car top needs to be cleaned 8/19/2024
MO Minimum : Elevators (I) - Pits (I)1 No No Pit and hoistway shall be cleaned of debris, oil & lint 8/19/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency alarm inoperable. Re-inspection required 5/16/2023
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes No Suspension ropes are below minimum diameter. Replace suspension means 9/5/2024
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes No Governor rope has excessive rouging and needs replaced 9/5/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Elevator car top needs to be cleaned 8/19/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit No No Clean debris and dirt from elevator hoistway 8/19/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Replace leaking seal on elevator traction machine 8/19/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Alarm bell in elevator cab does not work 9/5/2024
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes No Suspension ropes are below minimum diameter, need to replace suspension ropes. Re-inspection required 9/12/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Elevator cartop needs to be cleaned 9/13/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit No No Need to clean debris and dirt from elevator hoistway 9/13/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance No No Need to replace leaking seal on elevator traction machine 9/13/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Alarm bell in elevator cab does not work. Re-inspection required 9/12/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Missing ceiling tiles inside elevator. 1/23/2025