Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Provide firefighter operating instructions next to hall fire keyswitch 10/24/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Test and log firefighter operation monthly 10/24/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state operating certificate inside the machine room 10/24/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Post In Case of Fire signage next to lobby landing hall button fixture 10/24/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed 10/24/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x Emergency phone does not operate. 11/5/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone does not operate 11/30/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Retest auxiliary lowering unit after defective batteries are replaced 11/30/2022
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Firefighter phase 2 operation does not allow car calls to be registered while the doors are open. The doors have to be closed with the door close button before a car call can be registered. 14 days to fix this issue or elevator is red tagged 10/13/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency bell does not operate. 11/19/2020