Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Adjust counterweight buffer switch so corresponding cam engages switch roller on buffer compression. 10/7/2019
MO Minimum : Elevators (A) - Hoistways (A)16 Need to find shorted wire so that people don't get shocked in elevator car top 5/12/2023
MO Minimum : Elevators (A) - Hoistways (A)3 Hoistway door panels shall have fire tabs bent down
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone shall be made operational. Re-inspection required 1/23/2024
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Suspension ropes are undersized. Re-inspection required in 120 days 6/27/2022
MO Minimum : Elevators (S) - Fire Service (S)1 x x Phase II key switch in car is not correct. Replace with the appropriate phase II key switch 6/27/2022