Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (K) - Car Platforms and Car Slings (K)6 No No Upper left car guide shoe worn away. Unlined guide shoe assembly scraping rail, repair. 10/15/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)10 Car Floors No No Refasten cab floor rubber at car sill edge. 10/15/2019
MO Minimum : Elevators (I) - Pits (I)8 No No Sump pump does not work in pit. 9/26/2025
MO Minimum : Elevators (I) - Pits (I)1 No No Sump pump does not work in the pit. Pit needs to be cleaned of debris and water 9/26/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Replace worn and missing guide shoes 9/26/2025
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Machine room lighting shall not be less than 10 ft candles at floor level 9/26/2025
MO Minimum : Elevators (I) - Pits (I)1 No No Determine if the sump pump works, if not replace.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Elevator broke duing testing, need to perform the following to complete inspection: pressure relief, door pressure, emergency phone & emergency lighting. Re-inspection required 11/18/2024