MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Elevator broke duing testing, need to perform the following to complete inspection: pressure relief, door pressure, emergency phone & emergency lighting. Re-inspection required
|
11/18/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Machine room lighting shall not be less than 10 ft candles at floor level
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)10 Car Floors
|
|
|
Refasten cab floor rubber at car sill edge.
|
10/15/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Replace worn and missing guide shoes
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
|
|
Sump pump does not work in pit.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Sump pump does not work in the pit. Pit needs to be cleaned of debris and water
|
|
MO Minimum : Elevators
|
(K) - Car Platforms and Car Slings
|
(K)6
|
|
|
Upper left car guide shoe worn away. Unlined guide shoe assembly scraping rail, repair.
|
10/15/2019
|