Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) A permanent light fixture in the pit should have no less than 5 ft candles at the pit floor
A17.1-1996 : Elevators 1.2 - Stop switches 1001.2(a)(2) In car stop switch is broken.
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 7/26/2022
A17.1-1996 : Elevators 3.17 - Door and gate equipment 1001.2(c)(23) Bottom floor door is missing lower guides on each side, causing a gap between floor seal and door. Repair and reinspect within 30 days.
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) x Suspension ropes do not meet minimum requirements. 60 days to repair and reinspect. 7/26/2022
A17.1-1996 : Elevators 3.25 - Car, overhead, and deflector sheaves 208 x Repair or replace right car sheave, ropes imprinting sheave. Previously sited violation on 2019 inspection. 7/26/2022
A17.1-1996 : Elevators 3.25 - Car, overhead, and deflector sheaves 208 x Repair or replace right car sheave. Rope imprinting sheave. 10/6/2020
conversion conversion n/a Cab rear wall pushed out. No clearance between wall and cwt. Wall is actively scraping cwts as they pass each other in hoistway. Cab panel ribs bent beyond repair. Replace cab rear wall panels so wall maintains its required clearance. 3/14/2019