MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
A permanent light fixture in the pit should have no less than 5 ft candles at the pit floor
|
|
A17.1-1996 : Elevators
|
1.2 - Stop switches
|
1001.2(a)(2)
|
|
|
In car stop switch is broken.
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work.
|
7/26/2022
|
A17.1-1996 : Elevators
|
3.17 - Door and gate equipment
|
1001.2(c)(23)
|
|
|
Bottom floor door is missing lower guides on each side, causing a gap between floor seal and door. Repair and reinspect within 30 days.
|
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
x
|
|
Suspension ropes do not meet minimum requirements. 60 days to repair and reinspect.
|
7/26/2022
|
A17.1-1996 : Elevators
|
3.25 - Car, overhead, and deflector sheaves
|
208
|
x
|
|
Repair or replace right car sheave, ropes imprinting sheave. Previously sited violation on 2019 inspection.
|
7/26/2022
|
A17.1-1996 : Elevators
|
3.25 - Car, overhead, and deflector sheaves
|
208
|
x
|
|
Repair or replace right car sheave. Rope imprinting sheave.
|
10/6/2020
|
conversion
|
conversion
|
n/a
|
|
|
Cab rear wall pushed out. No clearance between wall and cwt. Wall is actively scraping cwts as they pass each other in hoistway. Cab panel ribs bent beyond repair. Replace cab rear wall panels so wall maintains its required clearance.
|
3/14/2019
|