A17.1-1996 : Elevators
|
3.5 - Normal terminal stopping device
|
210.2
|
x
|
|
Adjust lower direction switch so corresponding car cam opens it before cam opens lower final limit switch.
|
9/14/2020
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1001.2(d)12
|
x
|
|
Fire service audible buzzer/alarm inoperative.
|
9/14/2020
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Suspension ropes are undersized. Re-inspect required 120 days
|
2/27/2023
|