Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 3.5 - Normal terminal stopping device 210.2 x Adjust lower direction switch so corresponding car cam opens it before cam opens lower final limit switch. 9/14/2020
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)12 x Fire service audible buzzer/alarm inoperative. 9/14/2020
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Suspension ropes are undersized. Re-inspect required 120 days 2/27/2023