Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Hoistway doors are missing floor stencils
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Suspension ropes undersized with rouge, replace ropes by 12/17/21 1/7/2022
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x x Governor rope is undersized with rouge and birdaged 11/22/2021
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x x Suspension ropes undersized with rouge 11/22/2021
MO Minimum : Elevators (S) - Fire Service (S)1 x x Phase I recall inoperative. 9/16/2019
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal Fire jewel does not work during Phase I & II operation. 15 days to repair and reinspect. Only elevator in this building. 10/15/2021
MO Minimum : Elevators (S) - Fire Service (S)1 x x Phase I & Phase II fire service does not work correctly 11/22/2021
A17.1-2016 : Elevators 3.9 - Floor and emergency identification numbering 8.11.2.1.3(o) Hoist way doors are missing floor stencils
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980) 8.6.11.1 Removed Red Tag. Car now recalls and remains captured, but fireman's cab light still inoperable. 10/15/2019