A17.1-1996 : Elevators
|
2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater)
|
8.4.10.1.2 - Protection not functioning
|
x
|
|
Earthquake protective device shall work properly. Does not run to next floor and open doors. Reinspect Required by 9/24/21 or RED TAG
|
9/20/2021
|
A17.1-1996 : Elevators
|
3.10 - Hoistway construction
|
1001.2(c)(16)
|
|
|
Patch holes by car doors inside the hoistway
|
|
A17.1-1996 : Elevators
|
3.10 - Hoistway construction
|
1001.2(c)(16)
|
|
|
Patch holes by car doors inside the hoistway
|
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
x
|
|
Suspension rope undersized through hoistway.
|
10/14/2022
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
x
|
|
Suspension rope undersized throughout hoistway. Reinspect Required in 30 days
|
9/20/2021
|
A17.1-1996 : Elevators
|
3.28 - Counterweight and counterweight buffer
|
1001.2(c)(13)
|
x
|
|
Car does not meet minimum counterweight runby. Ropes need to be shortened.
|
12/21/2020
|