MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Suspension ropes are undersized. Reinspect within (60) days.
|
8/12/2021
|
MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)1
|
x
|
x
|
Wind-up safety rope did not reset. This renders safeties on the car disabled. This is also not a minimum of 3 turns on the drum when safeties set. Red tagged unit.
|
8/12/2021
|
A17.1-1996 : Elevators
|
2.6 - Ventilation
|
1001.2(b)(6)
|
|
|
Call cancel button is missing button cover
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Pit light needs a protective covering. It is missing
|
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
Cab lights need to be covered by a protective tube or light cover
|
|