MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Secure car top emergency exit in the closed position
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
x
|
Replace hoist cables due to diameter reduction. Cable stretched to excess allowing the counterweights to strike the buffer before the car reaches the up final limit
|
12/2/2021
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
x
|
Hoist ropes need shortened, counterweight landed on buffer springs before car could reach top final limit. Red tagged, Re-inspection required
|
12/6/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.8 Switch Keys
|
|
|
Fire panel and phase 1 switch shall be keyed alike
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Repair fire recall phase 2. Car not returning to phase 1 when phase 2 car switch is turned to off position
|
12/2/2021
|