A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
8.6.5.16.5
|
|
|
OSV set at 140 fpm with full load in cab. Car is rated for 150 fpm. Does not meet minimum requirements for correct operation. Needs to be set between 165 fpm and 210 fpm. Reinspect required in 90 days
|
|
A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
8.6.5.16.5
|
x
|
|
OSV would not function properly and would only set at 137 fpm, this value should be at least 165fpm. Re-inspection required
|
10/11/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone inoperative. Repair
|
9/14/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.2 - Stop switches
|
2.26.2.21
|
|
|
In car stop switch needs to be tested on fire service phase I recall A17.2 6.1
|
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
|
|
Car does not run contract speed w/load in cab. 67 fpm down w/full load & 46 fpm up w/full load. Valve need to be adjusted so that contract speed of 150 fpm can be achieved
|
|