Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.1 Examination and Maintenance of Packing Glands and Seals | x | Repack hydraulic cylinder due to excessive oil leakage. Finish removing oil return line from hoistway and machine room that was used for the scavenger pump. | 7/28/2022 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.13.3.4 | x | x | Phase II operation inoperative. Did NOT red tag. Does require reinspection after repair. | 6/5/2019 |