Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service (S)1 x x In car stop switch on, off, hold nomenclature is missing 11/14/2022
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light does not work
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) x Suspension ropes need to be shortened. Only 4.5 inches of counterweight runby 11/14/2022
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x x Governor rope has been oiled and greased. 11/14/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light is not working. Re-inspection required 1/30/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency lights shall be made operational. Re-inspection required