MO Minimum : Elevators (A) - Hoistways (A)13 There is black mold throughout hoistway. Mold abatement needs to be conducted 12/17/2024
A17.1-2016 : Elevators 2.29 - Car and counterweight safeties 2.17.3 x x The car would not set safeties as intended. This unit has been Red-tagged until the problem has been resolved and repaired. Re-inspection required
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x x Governor failed to set car safeties.
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Suspension ropes are undersized with rouge. Re-inspection required 8/30/2023