MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A code compliant MCP and related on-site documentation shall be provided in the machine room. Fire service testing must be documented monthly. All documentation blank.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be obtained and displayed in the equipment room.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Sewer piping/P-trap installed in ceiling (directly over elevator controller) shall have guttering and drainage properly installed to protect equipment.
|
|