MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A code compliant MCP and related on-site documentation shall be provided in the machine room. Fire service testing must be documented monthly. All documentation blank.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be obtained and displayed in the equipment room.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)7
|
x
|
|
Secondary pit stop switch is required with pit depth greater than 66".
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
x
|
|
Overspeed valve shall have current testing tag. Category 5 weight test required and overdue. Last tested 1999.
|
3/20/2025
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)7
|
x
|
|
Secondary pit stop switch is required with pit depth greater than 66".
|
3/20/2025
|