MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone shall be made operable. Re-inspection required
|
4/1/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests)
|
|
|
Need procedures for inspections and tests not described in A17.2.
|
9/2/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device.
|
9/2/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
This unit has an oil recovery system that returns oil that has leaked from the packing back to the pumping unit, this leakage is supposed to be monitored with a 5 gallon bucket.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
This unit has a oil recovery system that returns oil that has leaked from the packing back to the pumping unit, this leakage is supposed to be monitored with a 5 gallon bucket.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
The car door operator cover is missing and shall be reinstalled.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
The in car emergency telephone shall work with 24/7 support.
|
12/18/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans.
|
10/25/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning)
|
|
|
Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site.
|
9/2/2022
|
MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)1
|
x
|
x
|
Life jacket/plunger gripper would not stop car in the down direction. Unit Red-Tagged.
|
1/9/2019
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Unit has a Phase 1 fire service key switch located at the 1st and 2nd floor. The 2nd floor switch does not appear to function. Identify function of the switch or eliminate.
|
1/9/2019
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Provide Phase 1 fire service operating instructions on the 1st floor.
|
1/9/2019
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Unit has a Phase 1 fire service key switch located at the 1st and 2nd floor. The 2nd floor switch does not appear to function. Identify function of the switch or eliminate.
|
5/28/2019
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Provide Phase 1 fire service operating instructions on the 1st floor.
|
5/28/2019
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site.
|
9/2/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.4 Plunger Gripper Testing
|
x
|
|
This unit has a plunger gripping device that is supposed to be tested every 5 years and has not been tested since 2018. 5 year full load testing required within 30 days. Re-inspection required
|
4/1/2024
|