MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Alarm bell shall work with loss of main 120 V power.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
Yes
|
No
|
Emergency light shall work with loss of main 120v power.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
Yes
|
No
|
Car operating panel - top row buttons are damaged and shall be repaired or replaced.
|
2/26/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
Yes
|
No
|
Car door restrictor shal work at all floors.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
Yes
|
No
|
The in car emergency telephone shall be operational.
|
12/2/2019
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
Yes
|
No
|
The in car emergency telephone shall be operational.
|
10/28/2022
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
The emergency phone shall work.
|
2/6/2024
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
Yes
|
No
|
On fire service operation, a means shall be provided to cancel registered car calls.
|
10/28/2022
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
Yes
|
No
|
On fire service operation, a means shall be provided to cancel registered car calls. Customer will need to apply for a variance from the State of Missouri.
|
3/21/2023
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
The relief pressure shall be tested and a 15 minute standing test shall be performed.
|
2/4/2021
|
|
conversion
|
conversion
|
n/a
|
No
|
No
|
Need copy of current state operating certificate in machine room.
|
12/10/2019
|
|
conversion
|
conversion
|
conversion - reinspect
|
Yes
|
No
|
Door restrictor shall work on battery power.
|
11/7/2018
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Up-to-date operating certificate is required in the machine room.
|
4/3/2026
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
4/3/2026
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Operating Certificate EXPIRED 10/2023 due to open violations that need to be cleared so that new certificates can be issued. The displayed certificate is 2015-2016.
|
|