Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)10 Missing lock cover on access box allowing for non authorized entry. 12/30/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x PHONE NOT WORKING/DOES HAVE WORKING ALARM BELL 2/9/2024
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)5 A portion of the carlights not working 12/30/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x DOOR INTERLOCK ALLOWING DOOR TO OPEN IN MOTION (UNIT LOCKED OFF AT THIS TIME BY MECHANIC) 2/9/2024
MO Minimum : Elevators (I) - Pits (I)1 REMOVE OIL/DEBRIS FROM PIT 2/9/2024
MO Minimum : Elevators (I) - Pits (I)1 remove standing water and oil in pit 12/30/2019
MO Minimum : Elevators (I) - Pits (I)1 Remove water/oil and debris from pit 12/17/2020
MO Minimum : Elevators (I) - Pits (I)1 Remove oil/water standing in pit 12/17/2020
MO Minimum : Elevators (I) - Pits (I)1 Remove debris from pit 10/28/2022
MO Minimum : Elevators (I) - Pits (I)1 REMOVE STANDING OIL/WATER FROM PIT 10/25/2024
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)3 Water contaminated the system, contaminated oil removed from tank and replaced but jack and lines recontaminate oil needs repalced 12/30/2019
A17.1-2016 : Elevators 1.1 - Door Reopening Device 8.11.2.1.1(a) SAFETY EDGE ON INNER DOOR NOT WORKING 10/25/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) x EMERGENCY PHONE NOT RINGING TO SECURITY 10/25/2024