MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Emergency light not working. Bulbs
|
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
8.11.3.1.2(b)
|
|
|
Door to Elevator equipment room is not self closing due to insulation type material added around door frame and floor.
|
1/19/2021
|
A17.1-2016 : Elevators
|
1.15 - sign and operating device symbols
|
8.6.1.6.7
|
|
|
Need Phase I and Phase II Fire service operation instructions
|
1/19/2021
|
A17.1-2016 : Elevators
|
3.16 - Traveling cables and junction boxes
|
8.11.3.1.3(q)
|
|
|
Wiring raceway cover missing in hoistway top right side.
|
1/19/2021
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.7 Firefighter' Service Operating Procedures
|
|
|
Needs Phase II Instructions in car.
|
10/8/2024
|