Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.1 - Access to machine space 8.11.3.1.2(b) Door to Elevator equipment room is not self closing due to insulation type material added around door frame and floor. 1/19/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light not working. Bulbs
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 Need Phase I and Phase II Fire service operation instructions 1/19/2021
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures Needs Phase II Instructions in car. 10/8/2024
A17.1-2016 : Elevators 3.16 - Traveling cables and junction boxes 8.11.3.1.3(q) Wiring raceway cover missing in hoistway top right side. 1/19/2021