MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate shall be posted in the elevator machine room
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current operating certificate shall be displayed in the machine room
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work in the elevator cab. Repair or replace. Reinspection required
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Fire service could not be tested due to not having key. Key is unknown. Reinspect in 14 days
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Replace "roust-a-bout" oil supply pipe fittings with either cut, roll groove or threaded pipe fittings, in pit and equipment room. Re-insepction required.
|
1/22/2019
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Repair Alarm Bell - reinspection required
|
1/22/2019
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Rear car door will not stay open on Phase 2 fire service. Reinspect within 30 days.
|
11/5/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Repair machine room lighting. Bulb flickers on and off and it's not due to the bulb.
|
12/31/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
|
|
All automatic passenger elevators shall be provided with an alarm bell capable of being activated from inside the car & audible outside the hoistway
|
12/9/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Repair inoperative emergency light and alarm. Re-inspection required
|
1/23/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Car door open per code on front door the rear car does not operate as required by code
|
1/23/2024
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4 (Re-Inspection)
|
x
|
|
Supply line has roustabout fittings which have been outlawed by code since 1984. replace fittings with victraulic or threaded pipe.
|
1/23/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency bell does not work. Re-inspection required
|
1/23/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Emergency light does not work. Re-inspection required
|
1/23/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Rear door will not stay open on Phase 1 . Only elevator in the building, will allow 15 days to repair. Re-inspection required
|
1/23/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
On phase 2 fire service, the rear door will not remain open at the 2nd floor, needs repaired. Re-inspection required
|
12/31/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Elevator cab emergency lights do not work, needs repaired. Re-inspection required
|
12/31/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Bell and Phone not Functioning (Red Tag)
|
x
|
x
|
Elevator cab phone does not work, needs repaired. Red-tagged, Re-inspection required
|
12/31/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Bell and Phone not Functioning (Red Tag)
|
x
|
x
|
Elevator cab alarm bell does not work, needs repaired. Red-tagged, Re-inspection required
|
12/31/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
x
|
|
Install phase 1 & 2 operating instructions at both fireman's operation key switches. Re-inspection required
|
12/31/2024
|