Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate shall be posted in the elevator machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current operating certificate shall be displayed in the machine room
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone does not work in the elevator cab. Repair or replace. Reinspection required
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire service could not be tested due to not having key. Key is unknown. Reinspect in 14 days
conversion conversion conversion - reinspect x Replace "roust-a-bout" oil supply pipe fittings with either cut, roll groove or threaded pipe fittings, in pit and equipment room. Re-insepction required. 1/22/2019
conversion conversion conversion - reinspect x Repair Alarm Bell - reinspection required 1/22/2019
MO Minimum : Elevators (S) - Fire Service (S)1 x x Rear car door will not stay open on Phase 2 fire service. Reinspect within 30 days. 11/5/2020
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Repair machine room lighting. Bulb flickers on and off and it's not due to the bulb. 12/31/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) All automatic passenger elevators shall be provided with an alarm bell capable of being activated from inside the car & audible outside the hoistway 12/9/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Repair inoperative emergency light and alarm. Re-inspection required 1/23/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Car door open per code on front door the rear car does not operate as required by code 1/23/2024
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 (Re-Inspection) x Supply line has roustabout fittings which have been outlawed by code since 1984. replace fittings with victraulic or threaded pipe. 1/23/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency bell does not work. Re-inspection required 1/23/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light does not work. Re-inspection required 1/23/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Rear door will not stay open on Phase 1 . Only elevator in the building, will allow 15 days to repair. Re-inspection required 1/23/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x On phase 2 fire service, the rear door will not remain open at the 2nd floor, needs repaired. Re-inspection required 12/31/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Elevator cab emergency lights do not work, needs repaired. Re-inspection required 12/31/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Bell and Phone not Functioning (Red Tag) x x Elevator cab phone does not work, needs repaired. Red-tagged, Re-inspection required 12/31/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Bell and Phone not Functioning (Red Tag) x x Elevator cab alarm bell does not work, needs repaired. Red-tagged, Re-inspection required 12/31/2024
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage x Install phase 1 & 2 operating instructions at both fireman's operation key switches. Re-inspection required 12/31/2024