A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Cab phone line inoperative.
|
10/15/2019
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone in elevator cab does not work.
|
2/2/2021
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required.
|
12/3/2024
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The elevator alarm bell inside the elevator is not working. Check and repair the alarm bell for proper operation and passenger safety. Reinspection required.
|
12/3/2024
|
A17.1-1996 : Elevators
|
1.9 - Power closing of doors or gates
|
112.3
|
x
|
|
The bottom car door reopening device (electric eye) was not working on the day of inspection. Repair or replace the reopening device for passenger safety.
|
12/3/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Fire service Phase I is not working. Re-inspection required
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
After the call acknowledgement signals are sent, the two way voice communications shall be available between the car & authorized personnel. Re-inspection required
|
12/13/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)7
|
x
|
|
Door pressure too high, over 30 lbs, needs repair. Re-inspection required
|
11/30/2023
|